| Sign In | Join Free | My ecer.com.ru |
|
MOQ : 1
Load Way : Electronic Load
Loading Method : Dynamic Load
Weight : 0-100Kg
Application and Testing3 : Impulse Withstand Test
Application and Testing7 : Gas Insulated Switchgear (Gis) Test
Trademark : Sansion
Packaging Details : plywood case
Application and Testing1 : Dielectric Withstand Test
Max Diameter of Workpiece : 900mm
Accuracy Grade : 0.5
HS Code : 9030339000
Power Source : AC380V
Application and Testing6 : Transformer Impulse Test
Brand Name : Sansion
Type : Strength Testing Machine
Production Capacity : 100 Units/Month
Payment Terms : TT LC
Place of Origin : Chnia
Display : LCD Display
Control : Computer Control
Origin : China
Price : 1000
Specification : 1000mm*600mm*560mm
Application and Testing4 : Surge Arrester Test
Certification : CE SGS ISO9001
Mass Scope of Workpiece : <900kg
Maxcapacity : <1000KN
Application and Testing2 : Breakdown Voltage Test
Model NO. : SXCF
Oil Cylinder Position : Under
Application and Testing5 : Insulation Strength Test
Application and Testing8 : High-Voltage Cable Test
Transport Package : Plywood Case


| Parameter | Specification |
|---|---|
| Impulse voltage grade | 100kV-7200kV |
| Standard lightning wave | 1.2±30%/50±20%µS |
| Peak oscillation | 5% |
| Standard switching wave | 250±20%/2500±60%µS |
| Virtual front time of oscillating lightning wave | 15µS |
| Virtual front time of oscillating switching wave | 15µS-1µS |
| Minimum output voltage | 10%Un |
| Charging voltage instability | 1% |
| Synchronizing range | 20% |
| Synchronous discharge error rate | 2% |
| Ignition range | 10%-100% |
| Working time | 70%UN Discontinuous work (charge-discharge 300s/time) 70%nn Continuous work (charge-discharge 120s/time) |
| Generator efficiency | Lightning wave (no load) - 90% |
| Time to chopping | 2-5µS |



|
|
Lightning Impulse Voltage Tester Full Wave Impulse Generator For HV Withstand Testing Images |